3kw kettle

Avatar Image
Mr-H | 23:48 Tue 20th Nov 2012 | How it Works
12 Answers
We bought a new kettle yesterday, but since installation the socket ring main keeps blowing. I notice that the redundant kettle is 2.2kw whilst the new one is 3kw. Would this make a difference? A couple of further comments - when the mains tripped out, the tumble dryer and microwave were also on, as well as tv, sky box, freezer in the garage etc. I swapped the new kettle for the old, and have had no further problems. The new kettle is going back to the supplier tomorrow for a refund in case it's faulty, and we will buy a replacement approx the same power. Any ideas folks? Could it even be a wiring fault in the mains?
Gravatar

Answers

1 to 12 of 12rss feed

Best Answer

No best answer has yet been selected by Mr-H. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
Not a specialist but if you overload the ring it will trip. Have you tried running the kettle with other things unplugged? We had the same trouble when we put extra lights in the garage and needed to uprate the fuse.
I don't believe one should be able to overload a ring using normal appliances like that. Sounds as if there is a fault somewhere, probably with your new kettle. Is it the circuit breaker or the RCD that goes ?
One ought not need to "uprate" the fuse. If it is the right size and blows, it is doing it's job.
But it wasn't the right size......
With respect...

You shouldn't have been putting "extra lights in the garage" and then finding out the fuse wasn't the correct size so then you just "uprate" the fuse.

A fuse is, by design, meant to be the weak point, simply uprating a fuse can transfer the weak point to somewhere that doesn't blow so gracefully and with no harm.
I like your description of a fuse blowing gracefully Chuck :-)
It could be many things, including mains wiring with too light rating. If your house is older than 25 years it may be that this needs be replaced. We now have a lot more electrical appliances.

Take the above advice and DO NOT increase the rating of the fuses unless this has been checked by a qualified person.
-- answer removed --
What is it that blows? - an RCD at the consumer unit or the MCB breaker (a modern day fuse) specific to the ring main containing the kettle.
If the RCD, there is an earth leakage fault with the kettle, and you should return it.
If the MCB / fuse, you are overloading the main ring. Try Woofgang's advice - running the kettle with other things unplugged.
Chuck the wiring and all the rest was uprated....We had it done by a real certified electrician and have got the certificate to prove it.
Question Author
The RCD at the consumer unit kept tipping out. Kettle has now been returned as potentially faulty. Thanks for the advice.
Kettles are notorious for earth faults. You are not alone in finding a new one that was duff.