immersion heater thermostat

Avatar Image
WALT0193 | 11:18 Wed 18th Apr 2007 | DIY
3 Answers
Just need confirmation I am using the correct cable between the thermostat and switch. Presently using 2.5
2 core + unsheafed earth.
Nort sure why the earth is unsheafed.
Gravatar

Answers

1 to 3 of 3rss feed

Best Answer

No best answer has yet been selected by WALT0193. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
The correct flex that you need to use is 1,5mm 3core Butyl flex as it is heat resistant and flexible.
PVC twin and earth cable, when heated becomes brittle causing the breakdown of the insulation therby exposing bare cablel to the touch
goodlooking is 100% correct, on no account use ordinary cable, it must be heat resisting. long time since I heard it called Butyl, goodlooking you must be as old as me,
Question Author
Thanks g/looking and rays. I'm heading to B&Q